SIGN:PROTOCOL-INJECTION

Protocol packet injection

Type ID

SIGN:PROTOCOL-INJECTION

Security profile

Alerts of this type are visible in the following security profiles:

  • HIGH
  • PARANOID

Risk

The base risk for this alert is 6.

Cause

A correct protocol packet in the wrong context has been detected: this may be caused by an injection, network retransmissions, or a non compliant protocol implementation, and may cause equipment to operate improperly. Example: a correct GOOSE message sent with a wrong stNum/sqNum.

Solution

Investigate on the protocol implementation, the presence of retransmissions due to network configurations, and the possible presence of malicious actors.

Product versions

Guardian 18.0.0

Trace

Alerts of this type are expected to generate traces.

Deduplication key

  • Attribute DESTINATION_NODE_ID
  • Attribute TYPE_ID
  • Attribute TRIGGER_ID