SIGN:PROTOCOL-INJECTION
Protocol packet injection
Type ID
SIGN:PROTOCOL-INJECTION
Security profile
Alerts of this type are visible in the following security profiles:
- HIGH
- PARANOID
Risk
The base risk for this alert is 6.
Cause
A correct protocol packet in the wrong context has been detected: this may be caused by an injection, network retransmissions, or a non compliant protocol implementation, and may cause equipment to operate improperly. Example: a correct GOOSE message sent with a wrong stNum/sqNum.
Solution
Investigate on the protocol implementation, the presence of retransmissions due to network configurations, and the possible presence of malicious actors.
Product versions
Guardian 18.0.0
Trace
Alerts of this type are expected to generate traces.
Deduplication key
- Attribute
DESTINATION_NODE_ID - Attribute
TYPE_ID - Attribute
TRIGGER_ID